Display - Array Backfeed
Description- Detection of current into the array greater than –25 Amps for 10 seconds.
Resolution:
1. Check HMI Monitors, Main menu; polarity of “Export Power'”
2. Check for damaged modules
3. Verify GFDI fuse F3 is intact
Display - Array Backfeed
Description- Detection of current into the array greater than –25 Amps for 10 seconds.
Resolution:
1. Check HMI Monitors, Main menu; polarity of “Export Power'”
2. Check for damaged modules
3. Verify GFDI fuse F3 is intact