RNWBL Service Line

Submit a ticket My Tickets
Welcome
Login  Sign up

MMTCON Resetting Fault

 

MMTCON Isolation: 


  1. Begin by removing all connections – except for the application coding plugs – from the MMTCON except for the A1-X70 and A1-X1 24Vdc power supplies to the MMTCON. 
    1. Observe the behavior of the board to see if the cycling continues. It may be necessary to submit additional data or check the SD card data to see if the cycling is still occurring. 
    2. If the cycling continues, then the fault is likely internal to the board.