Display - Outlet Pressure
Description - Indicates that the stacks’ outlet pressure is less than or equal to the minimum outlet pressure(20 PSI) for 3 seconds while the pump is running.
Resolution:
Pressure entering the coolant pump: pump inlet
1. Verify Outlet Pressure reading on HMI: Monitor-menu
2. Check for coolant leaks
3. Check coolant Pressure Sensor/Transducer PT2 in LC Cabinet section: wiring
■ TB11-5 | TB11-12 | CANUX2 J6-8/3/(7-shield drain-wire)