Display - AC Surge 1
Description- Primary AC Surge Protector Failure AC Surge devices between CB1 and K8/K9/K10
Resolution- Replace AC Surge protector SS2 and/or SS4 in the AC Cabinet Section
■ Verify 30 A fuses F31 | F32 | F33
■ Verify ckt-wiring SS2-12 – 18RD513 – CAUX3-J3-2
■ Verify ckt-wiring SS4-11 – 18RD3360 – TB10-2 (+24 V)
■ Verify ckt-wiring 18RD3360A between SS2-11 – SS4-12